8.4.1. Register 2001 definition – New Status Word
Bit
Definition
0
Ready
1
Running
2
Tripped
3
Standby
4
Fire Mode
5
Reserved
6
Speed Set-point Reached (At Speed)
7
Below Minimum Speed
8
Overload
9
Mains Loss
10
Heatsink > 85°C
11
Control Board > 80°C
12
Switching Frequency Reduction
13
Reverse Rotation
14
Reserved
15
Live Toggle Bit
8.4.2. Register 2005 definition – IO Status Word
Bit
Definition
0
DI1 Status
1
DI2 Status
2
DI3 Status
3
DI4 Status
4, 5
Reserved
6
IP66 Switch FWD
7
IP66 Switch REV
8
Digital Output Status
9
Relay Output Status
10, 11
Reserved
12
Analog Input 1 Signal Lost (4-20mA)
13
Analog Input 2 signal Lost (4-20mA)
14
Reserved
15
IP66 Pot Input > 50%
www.emk-motor.de
Description
This bit is set if no trip and no mains loss, plus hardware enabled
This bit is set when drive is running
This bit is set when drive is under trip condition
This bit is set when drive is in standby mode
This bit is set if fire mode is active
Read as 0
This bit is set when drive is enabled and reaches speed set point
This bit is set when drive is enabled and speed less than P-02
This bit is set if motor current > P-08
This bit is set if mains loss condition happens
This bit is set if drive heatsink temperature over 85°C
This bit is set if control PCB temperature over 80°C
This bit is set if PWM switching frequency foldback is active
This bit is set when motor is in reverse rotation (negative speed)
Read as 0
This bit will toggle each time this register is read
Description
This bit is set when digital input 1 is closed
This bit is set when digital input 2 is closed
This bit is set when digital input 3 (AI-2) is closed
This bit is set when digital input 4 (AI-1) is closed
Read as 0
This bit is set when IP66 FWD switch is closed
This bit is set when IP66 REV switch is closed
This bit is set when digital output is active(24V) or Analog output > 0
This bit is set when user relay is closed
Read as 0
This bit is set when analog input 1 signal loss happens (4..20mA)
This bit is set when analog input 2 signal loss happens (4..20mA)
Read as 0
This bit is set when IP66 integrated pot input value > 50%