●"Floor debug", "Disinfection", and "Holiday mode" cannot be activated at the same with this function. When
doing so, a window will pop up, saying "Please disable the emergen. mode!".
●Upon power failure, "Emergen. mode" will back to "Off".
2.2.13 Holiday mode
[Operation Instructions]
This function is intended to let the heat pump run under the energy conservation mode so as to keep the room
temperature within a certain range, which then will prevent pipelines from suffering frostbites.
At the function setting page, select "Holiday mode" and set it to "On" or "Off".
[Notes]
●This function can be activated only when the control panel has been turned off, otherwise a prompt dialog box
will pop up, saying "Please turn off the system frist!".
●When "Holiday mode" has been activated, the operation mode will automatically switch to "Heat". Mode
setting and "On/Off" operation through the control panel will be unavailable.
●When "Holiday mode" has been activated, the control panel will automatically deactivate the "Weekly timer"
and "Preset mode"and "Clock timer" and "Temp.timer".
●Under the "Holiday mode", when the main unit is under the control of room temperature, the set point (room
temperature for heating) should be set to 10°C; when it is under the control of leaving water temperature, the set
point (leaving water temperature for heating) should be 30°C.
●When this function has been activated, "Floor debug", "Emergen.mode", "Disinfection", "Manual defrost",
"Preset mode", "Weekly timer", "Clock timer", and "Temp.timer" cannot be activated at the same time,
meanwhile a window will pop up, saying "Please disable the holiday mode!".
●This function will be memorized upon power failure.
2.2.14 Preset mode
[Operation Instructions]
At the function setting page, select "Preset mode" and go to the corresponding setting page.
At the time period setting page, each time period can be set to "Valid" or "Invalid".
The option "Mode" is used to preset the mode; "WOT-Heat" is used to set the leaving cold/hot water
temperature; "Start timer"/"End timer" is used to for time setting. After that, by touching the "Save" icon, all
settings will be saved.