Horizontal Vent Clearance
For horizontal vent, maintain 1 inch of clearance to the bottom and
sides of vent, and 3 inches of clearance to combustibles above the
vent pipe. See Figure 37.
Vertical Vent Clearance
For vertical vent, maintain a minimum 1 of inch clearance to
combustibles.
NOTICE: Maintain 1 of inch of clearance to combustibles around
vertical vent pipe. See Figure 36. For horizontal vent systems,
maintain a minimum 1 inch of clearance from the bottom and sides
of the vent to combustibles and a 3 inches of
to combustibles. See Figures 36 and 37.
vent pipe
VENT PIPE
TOP OF VENT
3" (76 mm)
1" (25 mm)
Horizontal Vent Clearances - Figure 37
ATTENTION: Cold climate installation recommendation: When
installing this unit against an exterior wall, the exterior wall must
be insulated to conform to applicable insulation codes. The
fireplace outer wrapper is not considered a thermal barrier and
can allow air infiltration. Care should be taken to properly seal
the chase area so air infiltration is kept to a minimum and drafts
do not occur through the fireplace.
Page 24
INSTALLATION (CONT'D)
clearance above the
1" MINIMUM CLEARANCE
AROUND VENT PIPE
Figure 36
COMBUSTIBLES NOT
ALLOWED IN SHADED
AREA
4" DIAMETER FLUE
6 5/8" DIAMETER
INTAKE VENT
1" (25 mm)
Vent Runs
In planning the installation, you must install certain components
before the fireplace is secured in position. These include the direct-
vent system, gas piping, and the electrical wiring.
The appliance can be mounted on any of the following surfaces:
1.
A flat, hard combustible or non-combustible surface.
2.
A raised wooden platform.
3.
Four corner supports(such as masonry blocks). These supports
must be positioned so they contact all four perimeter edges on
the bottom of the unit.
43902-0-1021