Adjustment of low speed is carried out using the LOW SPEED Trimmer which varies the output
voltage to the head/s of the motor/s (turn clockwise to increase speed). Adjustment is carried
out to establish the correct speed at the completion of opening and closing, depending on the
structure of the gate, or if there is any light friction that could compromise the correct working
of the system. The low speed is activated (DIP 8 OFF) when the gate leaf is 0.50-0.60 meters
away from the complete close or open position.
ELECTRONIC BRAKE
If the low speed in approaching is disabled (DIP 8 su ON), is preferable turn the DIP 7 ON to
enable at least the electronic brake that permits to win the gate leaf inertia when the gate
reaches the close or open limit switches.
ELECTRONIC BRAKE FOR FAST VERSION code BA03221 - BA03177:
The electronic brake is always enabled with FAST operators
The "weak version" of the electronic brake is enabled with DIP 7 OFF.
The "strong version" of the electronic brake is enabled with DIP 7 ON.
GRADUAL START
DIP 9 ON => the gate starts to move gradually for 1 second only.
LED WARNING
DL1 - programming activated (red)
DL2 - radio code programming (green) (CRX version only)
DL3 - open limit-switch contact (NC) (red)
DL4 - close limit-switch contact (NC) (red)
DL5 - gate closing M1 (red)
DL6 - gate opening (green)
DL7 - photocell contact (NC) (red)
DL8 - safety strip contact (NC) (red)
DL9 - Pedestrian opening button (red)
POINT C - MOTOR ROTATION DIRECTION CHECK
This operation is meant to help the installer during the installation (commissioning) and for
further future controls.
During this procedure, safety photocells and safety strip are not active.
1 - Unlock the operator with the Manual Release, install the limit switch plates, swing open the
leaf about halfway and lock the operator.
2 - Turn DIP 1 to ON position, LED DL1 starts blinking
3 - Press and hold the PROG button, the gate will open or close. Release the button and the gate
will stop. Press and hold again, the gate will move in the opposite direction.
The K control board has two movement leds
- DL6 the GREEN led for OPENING
- DL5 the RED led for CLOSING
4 - Press and hold the PROG button, if the gate opens with the green led on then you may
proceed to step 5.
If the gate moves in the wrong direction compared with the movement leds:
- turn OFF the main AC power
- reverse the V and W motor cables position (the blue motor cable must be always in the
U position)
- reverse the limit switch wires marked LSO and LSC
- turn ON the main AC power and check again the motor direction
5 - After 2 s motor starting and for the next 10 s motor working, the torque control is
automatically activated. Set the motor torque by the TORQUE Trimmer which varies the
output voltage to the head of the motor (turn clockwise to increase torque).
6 - After other 10 s motor working, the low speed control is automatically activated (DIP 8
OFF). Set the motor low speed by the LOW SPEED Trimmer to select the gate leaf low speed
in approaching.
FOR FAST VERSION code BA03221 - BA03177:
5 - After 1 s and within 5 s of continuous work, both in closing or opening, the electronic
clutch intervenes automatically. Adjust the force of the electronic clutch by turning the
appropriate trimmer TORQUE.
6 - After 5 s of continuous work, both in closing or opening, the deceleration is automatically
activated (if DIP 8 OFF). Adjust the low speed during the deceleration by turning the
appropriate trimmer LOW SPEED.
7 - Press and hold the PROG button to close completely the gate. Turn DIP 1 to OFF, the RED led
DL1 will stop blinking.
POINT D - PROGRAMMING
All the safety devices (photocells and safety strip) will be active, so they must be properly
installed and connected to the control board. Any changing of the safety devices input
state, will stop the procedure that must be repeated from the beginning.
1 - The gate must be fully closed.
2 - Turn DIP 2 to ON position, LED DL1 starts blinking
3 - Press PROG. Button, motor opens.
4 - Once reached the open position, the open limit switch will cut out motor and the gate
travelling will be stored. The gap of time between now (stop of motor) and the next pressing
of the PROG. button (see step 5 below) will be then stored as waiting time for Automatic
Closing feature.
5 - Press PROG. button, gate closes and the Automatic Closing time is stored (see DIP 3 function
to enable or disable the Automatic Closing feature).
6 - The LED DL1 will turn OFF, signalling exit from the Point D procedure.
Closing of the gate will be carried out at normal speed and only on approaching total
closing at low speed (depending on the adjustment of LOW SPEED trimmer).
7 - When the gate leaf reaches the close limit switch plate, the motor stops.
8 - Turn DIP 2 to OFF position.
POINT E - PROGRAMMING OF PEDESTRIAN OPENING (#)
All the safety devices (photocells and safety strip) will be active, so they must be properly
installed and connected to the control board. Any changing of the safety devices input
state, will stop the procedure that must be repeated from the beginning.
1 - The gate must be fully closed.
2 - Turn DIP 2 to ON position, the LED DL1 starts blinking quickly
3 - Immediately, turn also DIP 1 to ON position, the LED DL1 starts blinking slowly
4 - Press the pedestrian pushbutton PED. BUTT, the gate opens
5 - When the gate leaf is opened enough for the pedestrian crossing, press the pedestrian
pushbutton PED. BUTT to stop the travel (thus defining the opening stroke of the motor).
The gap of time between now (stop of the motor) and the next pressing of the PROG. button
(see point 6 below) will be stored as waiting time for Pedestrian Automatic Closing feature.
6 - Press the pedestrian pushbutton PED. BUTT, gate closes and the Pedestrian Automatic
Closing time is stored (see DIP 3 function to enable or disable the Automatic Closing
feature).
7 - Turn DIP 1 to OFF position.
8 - Turn DIP 2 to OFF position.
POINT F - PROGRAMMING RADIO CODES FOR COMPLETE OPENING
(UP TO 30 CODES - ONLY FOR CRX MODELS)
You can only programme the codes if the gate is closed.
1 - Position DIP 1 to ON and then DIP 2 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10 s.
3 - Press the remote control button (normally channel A) within the 10 s proscribed. If the
remote control has been correctly programmed, the DL2 LED (green) will flash once.
4 - The code programming time resets automatically so that you can programme the next
remote control.
5 - To finish programming, let 10 s pass and then press the PROG. button briefly. The red DL1
LED will stop flashing.
6 - Turn DIP 1 to OFF and DIP 2 to OFF.
PROCEDURE FOR DELETING ALL RADIO CODES USED ONLY FOR COMPLETE OPENING
You can only delete the codes if the gate is closed.
1 - Position DIP 1 to ON and then DIP 2 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10 s.
3 - Press and hold the PROG button for 5 s. The green DL2 LED will flash twice to confirm that
the stored codes have been deleted.
4 - The red programming DL1 LED remains active and you can programme new codes as shown
above if required.
5 - Turn DIP 1 to OFF and DIP 2 to OFF.
HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR COMPLETE OPENING
You can only check the memory if the gate is closed.
1 - Position DIP 1 to ON and then DIP 2 to ON.
2 - The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored).
3 - After this, the DL1 programming LED will remain active for 10 s, so that you can delete all
codes if required.
4 - Turn DIP 1 to OFF and DIP 2 to OFF.
POINT G - PROGRAMMING RADIO CODES FOR PEDESTRIAN OPENING
(UP TO 30 CODES - ONLY FOR CRX MODELS)
You can only programme the codes if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10 s.
3 - Press the remote control button (normally channel B) within the 10 s proscribed. If the