Minimum safety distances

Minimum internal distances
The installation niche must be made of non-flammable materi-
al. The minimum distances between the fireplace and walls are
shown in the drawing:
Minimum internal distances
A) Upper
50 mm
B) Rear
50 mm
C) Lateral
200 mm
Minimum external distances
Flammable objects and walls can not be placed within the high-
lighted area in the drawing:
Minimum external distances
C) Lateral
200 mm
D) Front
800 mm

Air grills

To avoid overheating of the unit, air recirculation with one or more openings must be created in the upper and lower part of the
cladding.
Observe the minimum dimensions shown in the drawing:
Air grills
E) Upper
Hot air outlet
F) Lower
Cold air inlet
GH) Laterals
(in case of installation
on a support)
Use and maintenance manual RBH 150 V - RBH 200 V
450 cm
2
500 cm
2
2 x 250 cm
2
B
E
F
A
C
D
C
E
G