FUNCTIONS MENU
IMPORTANT! Start programming by fi rst performing the following: MOTOR-TYPE SETTING (A1),
OPENING DIRECTION (F54), TOTAL STOP (F1) and TRAVEL CALIBRATION (A3)
Programming the features is to be done when the operator is stopped.
You can memorize up to 25 maximum users.
F1 Total stop [1-2]
NC input – Gate stop that excludes any automatic closing; to resume movement, use the control device. The
safety device is inserted into [1-2].
F2 Input [2-CX]
NC input – Can associate: C1 = reopening during closing by photocells, C2 = reclosing during opening by
photocells, C3 = partial stop, C4 = obstruction wait, C7 = reopening during closing by sensitive safety-edges,
C8 = reclosing during opening by sensitive safety-edges.
F3 Input [2-CY]
NC input – Can associate: C1 = reopening during closing by photocells, C2 = reclosing during opening by
photocells, C3 = partial stop, C4 = obstruction wait, C7 = reopening during closing by sensitive safety-edges,
C8 = reclosing during opening by sensitive safety-edges.
F5 Safety test
After every opening or closing command, the board will check whether the photocells are working properly.
 The safety test is always active for wireless devices.
F6 Maintained action
The gate opens and closes by keeping the button pressed. Opening button on contact 2-3P and closing button
on contact 2-7. All other control devices, even radio-based ones, are excluded.
F7 Command [2-7]
From the control device connected to 2-7, it performs the (open-close-invert) step-step, (open-stop-close-stop),
sequential, open or close command.
F8 Command [2-3P]
From the control device connected to 2-3P, it performs a partial (1) or total opening (2) of the gate.
 The partial opening time is adjusted on function F 71.
F9 Obstruction detection
with motor idle
With the gate closed, opened or totally stopped, the gearmotor stays idle if the safety devices, that is, photocells
or sensitive safety-edges detect an obstruction.
F10 Gate-open signal output
It signals the gate status. The signal device is connected to contact 10-5.
F11 Encoder
Managing slow-downs, obstruction detections and sensitivity.
F12 Slowed-down departure
With each opening and closing command, the gate starts moving slowly for a few seconds.
OFF = Deactivated (default) / ON = Activated
OFF = Deactivated (default) / C1 / C2 / C3 / C4 / C7 / C8
OFF = Deactivated (default) / C1 / C2 / C3 / C4 / C7 / C8
0 = Deactivated (default) / 1 = CX / 2 = CY / 4 = CX+CY
OFF = Deactivated (default) / ON = Activated
0 = Step-step (default) / 1 = Sequential / 2 = Open / 3 = Close
1 = Partial opening / 2 = Open
OFF = Deactivated (default) / ON = Activated
0 = lit when gate is open or moving (default) /
1 = when opening it fl ashes intermittently every half-second,
when closing it fl ashes intermittently every second,
stays lit when gate is open
is off when gate is closed
OFF = Deactivated / ON = Activated (default)
OFF = Deactivated (default) / ON = Activated