4. Electrical connection / 5. Commissioning / function test
GB
Normally open
With capacitive load, connecting cables longer than 50 m or connec-
tion to a PLC with capacitive input circuit, a 22 Ω resp. 47 Ω (10 VA
contacts) resistor is required to be connected in series to limit current
spikes.

5. Commissioning / function test

Switch on the power supply to the connected control unit
Fill the vessel and check the function of the magnetic operated
float switching points
The function test can also be conducted manually on the removed
switch.
6
WIKA Operating instructions Magnetic operated float switches Model RSB
Normally closed
Overloading the magnetic float switches may lead to
the destruction of the reed switch, which may cause a
malfunktion to the control circuitry and harm to persons
or goods. The maximum switch capacity values given in
the chapter "Technical data" and the Data Sheet must
not be exceeded.
Change over