Installat ion and co nnection of twin booster sets with
CONNECT ION
T ERMIN AL
BOARD
ALARM
OUTPUT
such that operation of one pump only is not s ufficient, the sec ond pump with Brio Top (SLAVE dev ice) is
started up. O n progressive c losure of the util ities , the reduction in the s ystem flow rate leads first to the
shutdown of the secondary pump on whic h the Brio Top is ins talled, later followed by the va riable speed
pump on which Sirio is ins talled. The f low rate le vel at wh ic h the secondary pump is shut down depends
on the value set in the parameter "Deactivation threshold" of the Brio Top; a higher value in this
parameter leads to a quicker deactivation of the second pump, while a lower value maintains the
"SLAVE" pump in operation even at lower flow rates .
If Sirio, i.e. the current MASTER devic e, shuts down due to a power failure, or blocks due to a fault,
sys tem control is trans ferred to the Brio Top device, which then immediately becomes the new MASTER
to enable the system to c ontinue operation. However, in this cas e operation at c ons tant pres sure is no
longer guaranteed, as there is no variable s peed device. It is rec ommended to install an expans ion
ves sel of at leas t 5-8 litres , to prevent, in the event of a fault on the Sirio devic e, Brio Top from activat ing
exc es sively frequent s tart-ups.
The programmed values of Pmin and Pmax must be the same on both devices.
ГК Водная техника info@water-technics.ru (495) 771 72 72 www.water-technics.ru
Интернет-магазин info@wtpump.ru (499) 937 50 61 (800) 505 78 67 www.wtpump.ru
INST ALLAT ION: install the Brio Top
on the delivery line of the s ec ondary
pump and the Sirio in verter on the
main variable s peed pump. Connec t
the outlet connector of each device to
the delivery manifold without inserting
any type of check valve. Connect the
intake lines of the pumps to the
common suction manifold, inserting a
check valve for each pump to prevent
drainage when stopped. Brio Top and
Sirio can be mounted vertically or
horizontally.
CONNECT IO N: the connec tion between the Brio Top
a nd Sirio devic es is by means of an uns hielded cable
2)
(4x0.5 mm
as s hown in the diagram alongside. The
maximum length of the c able is 100 cm including
s tripped sections.
A pre-as sembled connection cable is available, w ith
terminals
and
numbered wires) code no. SR-
CBL4X05-100). For Brio Top the operating mode
mus t be set to "P+P" and the parameter Aux. Con. to
"4". In the case of Sirio it is s ufficient to s et the
parameter "Aux. Con." to "1".
O PERATIO N: when switc hed on, the Sirio device
always sets to MASTER s tatus and is ass igned the
role of main controller. O n opening of the utilities,
Sirio starts up the pump first; if the water demand is
159
Sirio
inverter