Gas Supply - Empire Comfort Systems Mantis Instructions D'installation

Masquer les pouces Voir aussi pour Mantis:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

All gas piping must be installed in compliance with local codes
and utility regulations. In the absence of local codes the installa-
tion must comply with NFCG NFPA 54/ANSI Z223.1. CAN/CGA
- B149(.1 or .2) installation code.
Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Where permitted flexible gas connectors must be certified to the
following standards:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tub-
ing and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the author-
ity having jurisdiction. The state of Massachusetts requires that a
flexible appliance connector cannot exceed three feet in length.
A drip leg should be installed in the vertical gas supply pipe run to
the unit.
Manual Shut-off Valve
Some local regulations require the installation of a manual shut-off
valve and ground joint union external to the appliance. The shutoff
should be accessible for service and/or emergency use. Consult
the local utility or gas supplier for additional requirements regard-
ing the placement of the manual shut off valve. Compounds used
on threaded joints of gas piping shall be resistant to the action of
liquefied petroleum gases.
Leak Testing
WARNING - FIRE OR EXPLOSION HAZARD
Never test for leaks with an open flame. Check all connec-
tions using a commercially available soap solution. A fire or
explosion may result causing property damage, personal
injury or loss of life. Failure to follow the safety warnings
exactly could result in serious injury, death or property
damage.
After gas piping to the heater is complete, all connections must be
tested for gas leaks. This includes pipe connections at the main
gas valve, emergency shutoff valve and flexible gas connectors
(if applicable). The soap and water solution can be applied on
each joint or union using a small paintbrush. If any bubbling is
observed, the connection is not sealed adequately and must be
retightened. Repeat the tightening and soap check process until
the bubbling ceases.
Important Note:
When pressure testing the gas supply lines at pressures
greater than ½ psig (14 in. w.c.), the gas supply piping system
must be disconnected from the appliance to prevent damage
to the gas control valve. If the test pressure is less than or
equal to ½ psig (14 in. w.c.), close the manual shut-off valve.
31793-3-1015
All manuals and user guides at all-guides.com

GAS SUPPLY

Pressure Testing of the Gas Supply System
1.
2.
3.
To check the inlet pressure to the gas valve, a 1/8 inch N.P.T.
plugged tapping, accessible for test gauge connection, must
be placed immediately upstream of the gas supply connection
to the appliance.
The appliance and its individual shutoff valve must be dis-
connected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/2 psig.
The appliance must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig.
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
In Inches
Nat.
0-10 feet
1/2
10-40 feet
1/2
40-100 feet
1/2
100-150 feet
3/4
Tubing, Type L
Outside Diameter
In Inches
L.P.
Nat.
L.P.
3/8
1/2
3/8
1/2
5/8
1/2
1/2
3/4
1/2
1/2
7/8
3/4
Page 9

Publicité

Table des Matières
loading

Table des Matières