General Information

These instructions
ƒ inform about the use of the current limitation module E82ZJ004 and describe how to
install them.
ƒ are only valid
– for the current limitation module E82ZJ004,
– together with the Mounting Instructions/Operating Instructions of the
corresponding controller.
Range of application
The current limitation module E82ZJ004 reduces the switch-on current of the controller.
Thus it is possible to use smaller mains contactors.
The current limitation module E82ZJ004 can be used together with drive controllers which
use a mains current of ≤ 20 A for every phase. Every phase needs its own current limitation
module.
General data and applicaton conditions
Field
Rated current
Closing resistor at 25 °C
Type of protection
Dimensions (W x H x D)
Mounting
Observe national and regional regulations (e. g. VDE0113, EN 60204)!
Stop!
Frequent, cyclic mains switching heats up the current limitation module
E82ZJ004. Therefore, please observe:
With cyclic mains switching, wait at least 3 minutes before you restart the
unit. Otherwise the functionality of the current limitation module cannot be
ensured!
EDK82ZJ004 DE/EN/FR 3.0
General information
Values
20 A
5
IP20
approx. 43 mm x 91 mm x 60 mm
DIN rails 35 x 15 or 35 x 7.5