LAW 6IMR - LAW 14ITR
Step 4: Flanging
Flanging must be carried out as follows with a flanging tool
for R-410A refrigerant as shown in the figure.
External diameter
mm
9.52
15.88
Hold the copper pipe steady in a mould with the dimensions
shown in the bottom table.
Step 5: Checks
Compare the flanging with the figure on the right.
If the flanging is visibly damaged, cut the relevant section off
and repeat the flanging.
EN-10
"A"
Inch
mm
3/8
1.5 ~ 1.7
5/8
1.6 ~ 1.8
452162.66.09 · FD 9512
7.1.3 Pipe connections on the indoor unit
The pipe connection on the indoor unit takes place in two steps.
Read the following instructions carefully.
Step 1: Initial fastening
Align the centre of the pipe and tighten the screw nuts by
hand.
Step 2: Fastening
Tighten the screw nuts with a spanner.
Torques
External diameter
mm
9.52
15.88
7.1.4 Pipe connections on the outdoor
unit
The pipe connection on the outdoor unit takes place in steps.
Step 1: Determining the direction in which the
pipes are to run
The pipes can be connected in four directions
Torque
Inch
Nm
3/8
34 - 42
5/8
65 - 81