Set-up

5.1 General Information

The device should always be installed on a permanently smooth,
even and horizontal surface. The frame should lie tight on the
floor all the way round to guarantee sufficient sound insulation
and to prevent water-carrying parts from cooling down.If this is
not the case, additional insulation measures may be necessary.
If this is not the case, additional insulation measures may be nec-
essary. Natural ground, e.g., lawn should be below the air intake
and air outlet vents.If the installation conditions differ (installation
on a platform or flat roof) or there is a greater risk of the heat
pump tipping over (due to an exposed position or high wind ex-
posure), additional protection against tipping over must be pro-
vided. The responsibility for the heat pump installation lies with
the specialist system construction company. During the installa-
tion, local requirements such as building regulations, static load
of the building, and wind exposure must be accounted for.
It must be possible to carry out maintenance work without hin-
drance. This can be ensured by maintaining a clearance of 1.2 m
to any fixed walls.
ATTENTION!
Do not restrict or block the area around the air intake or outlet.
www.dimplex.de
All manuals and user guides at all-guides.com
452158.66.10 · FD 9208

5.2 Condensed Water Pipe

Condensate that forms during operation must be drained off
frost-free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensate pipe must have a mini-
mum diameter of 50 mm and must be fed into a sewer in such a
way that it is safe from frost. Do not discharge the condensate di-
rectly into clearing tanks or cesspits, as aggressive vapours or a
condensed water pipe which has not been laid in a frost-free
manner could destroy the evaporator.
ATTENTION!
The frost line can vary according to the climatic region. The regulations
of the countries in question must be observed.
6

Installation

6.1 General Information
The following connections need to be established on the heat
pump:
Flow and return flow of the heating system
Condensate outflow
Control line to the heat pump manager
Voltage supply
LA 26HS
EN-5