Transport; Set-Up; General Information; Condensed Water Pipe - Dimplex LIK 8TES Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LIK 8TES
5

Transport

CAUTION!
When transporting the heat pump, ensure that it is not tilted
more than 45° (in any direction).
Use a pallet for transporting the heat pump to the final installa-
tion location. The basic device can be transported with a lift
truck, hand truck or by means of 3/4" pipes fed through the
holes in the base plate or frame.
CAUTION!
The heat pump and the pallet are only joined by the packing
film.
Before using the holes in the frame, it is advisable to remove
each of the side panel assemblies. This is done by loosening
each of the two screws at the base and then withdrawing the
panels by unhooking them from above. Rehang the panels by
gently pushing them in an upwards direction.
3.
3.
1.
1.
2.
Opening the cover
After the transport, the transport securing device is to be re-
moved on either side at the bottom of the unit.
CAUTION!
The transport securing device is to be removed prior to
commissioning.
www.glendimplex.de
1.
1.
2.
2.
1.
Closing the cover
Remove/screw in
transport lock
452161.66.20a · FD 0106
6

Set-UP

6.1 General Information

The heat pump is designed for installation in a corner. Other in-
stallation locations are also possible in combination with an air
duct (available as an accessory) on the air outlet side.
The air-to-water heat pump must be installed in a frost-free, dry
room on an even, smooth and horizontal surface. The entire
base of the frame should lie directly on the floor to ensure an
adequate soundproof seal. If this is not the case, additional
sound insulation measures may be necessary.
The heat pump must be installed so that maintenance work can
be carried out without being hindered. This can be ensured by
maintaining a clearance of 1 m in front and to the left of the
heat pump. The side panel assemblies must not be covered by
connecting pipes.
1 m
Never install the device in rooms subject to high humidity. Con-
densation can form on the heat pump and air circuit if the hu-
midity exceeds 50 % and the external temperature is below
0 °C.
Neither frost nor temperatures higher than 35 °C must occur in
the installation location at any time of the year.
If the heat pump is installed on an upper storey, the load-bear-
ing capacity of the ceiling should be checked. On account of
the acoustics, measures for isolating possible vibrations should
also be very carefully planned in advance as well. Installation on
a wooden floor is not recommended.

6.2 Condensed Water Pipe

Condensate that forms during operation must be drained off
frost-free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensate pipe must have a mini-
mum diameter of 50 mm and must be fed into a sewer in such
a way that it is safe from frost. Do not discharge the condensate
directly into clearing tanks or cesspits, as aggressive vapours or
a condensed water pipe which has not been laid in a frost-free
manner could destroy the evaporator.

6.3 Sound

To prevent solid-borne sound from being transmitted to the
heating system, a vibration-damped connection should be
used for connecting the heat pump with the heating system (in-
stall the supplied hose connections free of strain).
Installed air ducts should be sound-isolated from the heat
pump to prevent the transmission of solid-borne sound to the
ducts.
If both air openings are connected directly to a wall opening,
the ventilator terminals can be reversed from a delta to a star
connection (see information in the ventilator terminal box).
English
1 m
EN-5

Publicité

Table des Matières
loading

Table des Matières