Télécharger Imprimer la page

Accessories; Control Line; Brine Circuit Manifold; Transport - Dimplex SI 30CS Instructions D'installation Et D'utilisation

Publicité

Les langues disponibles

Les langues disponibles

4
4

Accessories

4.1 Control Line

Two control lines are used to connect the heat pump controller to
the basic control as well as the basic control to the connection
box. They are available in various lengths.

4.2 Brine Circuit Manifold

The brine circuit manifold merges the individual collector loops of
the heat source system into a single main pipe which is con-
nected to the heat pump. Integrated ball valves allow the individ-
ual brine circuits to be shut off for de-aeration purposes.
5

Transport

A lift truck is suited for transporting the unit on a level surface.
Carrying straps may be used if the heat pump needs to be trans-
ported on an uneven surface or carried up or down stairs. These
straps can be passed directly underneath the wooden pallet. Al-
ternatively, the device may be raised using eye bolts which can
be screwed into the corners of the base frame.
ATTENTION!
The heat pump is not secured to the wooden pallet.
E-4
All manuals and user guides at all-guides.com
The heat pump must not be tilted more than 45° (in any direction).
6

6.1 General Information

The unit must be installed indoors on a level, smooth and hori-
zontal surface. The entire base of the frame should lie directly on
the floor to ensure a good soundproof seal. If this is not the case,
additional sound insulation measures may be necessary.
The heat pump must be installed so that maintenance work can
be carried out without hindrance. This can be ensured by main-
taining a clearance of approx. 1 m in front of and on each side of
the heat pump.

6.2 Acoustic Emissions

The heat pump operates silently due to efficient sound insulation.
To prevent noise transmission to the foundation, a suitable,
sound dampening rubber mat should be placed underneath the
base frame of the heat pump.
To prevent any sound from being transmitted to the heating sys-
tem, we recommend connecting the heat pump to the heating
system by means of hose sections.