1.
Strip the cable jacket for approximately 70 mm
(2.75") from the end of the cable, and thread the
wires through the gland
2.
Connect the wires to the terminals as shown
above: the polarity is identified on the terminal
block.
3.
Tighten the gland to form a good seal.
4.
Close the cover and tighten screws: please do
not overtighten screws. Recommended torque is
1.1 to 1.7 N-m (10 to 15 in-lb).
.
RUN Mode and PROGRAM Mode
SITRANS Probe LU has two modes of operation: RUN and PROGRAM.
SITRANS Probe LU automatically starts in RUN mode when power is applied, and detects the
material level. The primary reading displays the material level (in meters) referenced from
Empty (process empty level). This is the default start-up display mode.
System status is displayed on the LCD, or on a remote communications terminal.
RUN Mode Display
Use the hand programmer to control the display.
Normal operation
2
3
1
6
1 – Primary Reading (displays level, distance, or volume
2 – Secondary Reading (displays Parameter number for Auxiliary Reading
3 – Echo status indicator: Reliable Echo
4 – Units or Percent
5 – Active bar graph represents material level
6 – Auxiliary Reading (depending on the parameter selected, it displays milliAmp value,
distance, or echo confidence, with units where applicable.)
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
2.
For details on displaying flow instead of volume, please see P050 in the full manual.
3.
Press
to display the auxiliary reading field when in RUN mode.
Page EN-6
SITRANS Probe LU (HART) – QUICK START MANUAL
1
.
1
2 3
4
5
m
or Unreliable Echo
terminals for
loop current
Failsafe operation
3
1
6
2
, in either units or percent).
3
cable
4
5
m
)
7ML19985QR81