Télécharger Imprimer la page

ABB TTF300 Note De Mise En Exploitation page 69

Convertisseurs de mesure de température pour montage local
Masquer les pouces Voir aussi pour TTF300:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 71
6.4.3
Intrinsically Safe FM
I.S. Class I Div 1 and Div 2, Group: A, B, C, D or
I.S. Class I Zone 0 AEx ia IIC T*
Temp. Ident: T6 T
56 °C, T4 T
amb
U i / V
= 9V, I i / I
< 65.2 mA, P i = 101 mW
max
max
C i = 0.4 µF; L i = 0
Control Drawing: SAP_214 748
6.4.4
Non-Incendive FM
N.I. Class I Div 2, Group: A, B, C, D or
Ex nL IIC T*, Class I Zone 2
Temp. Ident: T6 T
60 °C, T4 T
amb
U i / V
= 9V, I i / I
< 65.2 mA, P i = 101 mW
max
max
C i = 0.4 µF; L i = 0
Control Drawing: SAP_214 751
6.4.5
Intrinsically Safe CSA
I.S. Class I Div 1 and Div 2; Group: A, B, C, D or
I.S Zone 0 Ex ia IIC T*
*Temp. Ident T6 T
56 C, T4 T
amb
U i / V
= 9V, I i / I
< 65,2 mA; P i = 101 mW
max
max
C i < 0,4 F µ , L i = 0
Control Drawing: SAP_214 749
6.4.6
Non-Incendive CSA
N.I. Class I Div 2, Group: A, B, C, D or
Ex nL IIC T*, Class I Zone 2
*Temp. Ident T6, T
60 °C, T4 T
amb
U i / V
= 9V, I i / I
< 65.2 mA, P i = 101 mW
max
max
C i < 0.4 µF, L i = 0
Control Drawing: SAP_214 750
Change from one to two columns
CI/TTF300-X1
85 °C
amb
85 °C
amb
85 °C
amb
85 °C
amb
TTF300
Type B LCD HMI
EN - 33

Publicité