WITCHES SETTING

3.3.1 Description

SW1202 : Battery
charger's ID
(1, 2, 3 and 4)
The CDS4 chargers are equipped with switches to configure the charger according the battery type and the
application (see section 3.3.2).
2 charging modes are available (SW1201) :
-
The BOOST function enables a faster charge of the batteries. This function is timed controlled (see section
3.3.2) and is automatically switched off when the battery is fully charged : BOOST stops when batteries current
< 20% of charger rated current. The BOOST function can also be disabled by means of a switch (E).
-
The REFRESH function enables to apply periodically a voltage step to maintain the battery, to promote its
equalization and prevent from any sulphation. This function is activated by means of a switch (F).
When communication Bus (CAN Bus or LIN Bus) is used, a unique ID (idenfier) must be selected. This ID shall be
selected from 0 to 15 (SW1202):
-
-
ADJUSTMENT
INDICATORS
Switches setting
1
2
3
0
0
0
1
0
0
FACTORY SETTING
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
Master/Slave positions
ID
LIN Bus only (Chargers in parallel)
4
0
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
1
8
1
9
1
10
1
11
1
12
1
13
1
14
1
15
SW1201 : Boost (E)
and Refresh (F)
SW1200 : Battery
(A, B, C et D)
Master
Slave n°1
Slave n°2
Slave n°3
settings
36