Setting According To The Batteries Type - ENAG CDS4 Série Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.3.2 Setting according to the batteries type

Switches setting
A
B
C
D
0
0
0
0
1
0
0
0
0
1
0
0
1
1
0
0
0
0
1
0
1
0
1
0
0
1
1
0
1
1
1
0
0
0
0
1
1
0
0
1
0
1
0
1
0
1
1
1
1
1
1
1
(*) Voltage on + BAT 1, + BAT 2 and + BAT E with 10% of the rated current and a tolerance of +/- 1%.
The voltages values must be halved for 12V batteries .
(
)
**
REFRESH is not advised for certain types of AGM batteries
(***) Battery Management System
Some specific settings are possible – please consult us.
Description of the
battery type
Opened type bat
free electrolyte (wet)
Classic sealed type bat
(Sealed Lead)
GEL type bat
AGM type bat**
Spiral type bat
Tin calcium lead bat
Wintering or standby
sealed bat
Stabilized DC power
supply
SPE1 open type bat
Lithium Iron Phosphate (
LiFePO4 ) with BMS
(***)
STORMLINE Bat
FLOATING
BOOST
VOLTAGE*
VOLTAGE*
26,8V
28,2V
27,6V
28,8V
FACTORY SETTING
27,6V
28,8V
27,2V
28,8V
27,2V
28,8V
28,8V
30,2V
26,8V
26,8V
24,0V
24,0V
26,4V
29,6V
27,6V
28,8V
27,4V
29,0V
Reserved for CAN Bus
Reserved for remote display SEEL016358
Maximum duration
Maximum duration
of BOOST at
of ABSORPTION at
+/- 5% T
BOOST
2H
2H
2H
2H
2H
2H
0H
0H
2H
6H
2H
+/- 5% T
ABS
4H
4H
4H
4H
4H
4H
0H
0H
4H
1H
6H
37