I
3.4
NTERFACES AND ACCESSORIES
J1201 et J102 :

CAN Bus

3.4.1 Temperature compensation

SEEL016946 temperature probe enable the compensation of Absorption voltage and
Floating Voltage depending on the ambient temperature of the battery room.
The coefficient used is -18mV/°C for 12V model and -36mV/°C for 24V models.
Temperature is not compensated when Wintering (or standby sealed bat), Stabilized DC power supply and Lithium
Iron Phosphate (LiFePO4) with BMS settings are selected
3.4.2 CAN Bus
The battery charger offers two receptacles matching with connectors Molex Microfit 3.0, 6 circuits (reference 43025-
0600).
Documentation n° 1336205REG_CAN (hardware and software specification) Is available upon request.

3.4.3 Parallel operation

It is possible to connect up to 4 battery chargers in parallel with the parallel connection kit SEEL017094.

3.4.4 Remote display

The battery charger supports the remote tactile colour display SEEL016358.
X1200 : ENAG LIN Bus :
- Remote display
- Parallel operation control
-
.
X1201 : Battery