Update Time Of The Display And Response Time Of Outputs - Kübler 573 Serie Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

• Press once more "Cmd" to display the actual analogue input signal. Now arrange for the
desired analogue input signal of the first interpolation point (with combined modes
please arrange for both analogue signals)
• When you read the x-value of your first interpolation point in the display, press "Cmd"
again. This will automatically store the actual display value to the P01_x register, and
for about 1 second you will read "P01_y " on the display, followed again by the same
reading stored previously.
• This display value now can be edited to the desired P01_y value, like a regular
parameter
• When you read the desired P01_y value in your display, store it by pressing "Cmd"
again. This will automatically cycle the display to the next interpolation point P02_x.
The unit will examine the constraint valid for the x-values of interpolation points.
Every interpolation point must be higher than its preceding point.
Where this constraint is breached, all 6 decimal points will blink automatically as a
warning. Pressing the CMD key will not store the illegal value, but result in an error text
"E.r.r.-.L.O." as a warning.
• Once you have reached and stored the last interpolation points P16_x/y, the routine will
restart with P01_x again, and you are free to double-check your settings once more.
• To conclude the Teach procedure, press the ENTER key. As a result you will read "StOP"
for about 2 seconds, before the unit returns to the normal operation. All linearisation
points will at the same time be finally stored.

8.4. Update time of the display and response time of outputs

Parameter "UPdAt" allows setting a variable update time for the display (see section 6.1).
The response time of the optocoupler outputs results from the sum of the selected
update time and a constant 3 msec. propagation delay of the optocoupler circuit itself.
Hence, the minimum delay time of the switching outputs to changes of the analogue
input is about 53 msec.