Switch Ghg 265 - Eaton CROUSE-HINDS GHG 266 Mode D'emploi

Masquer les pouces Voir aussi pour CROUSE-HINDS GHG 266:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Dimensions in mm
GHG 265.., 125 A 3- / 4-pole
GHG 266 ..., 180 A 3-pole
EXKO 2247 ..., 125 A 6-pole
EXKO 2247 ..., 180 A 6-pole
X = fixing dimensions
18
Explosion-protected switch
20 A - 180 A
1�8
Switch GHG 265 ��� (125 A)
EC type examination certificate:
Marking acc. to 2014/34/EU and standard:
IECEx certificate:
Category of application:
*The IP Degree of protection class can be mentioned separately on the type lable.
Rated voltage:
Rated current:
Perm. short circuit back-up fuse:
Switching capacity AC 3:
Cable entries (standard version):
suitable cables and test torques of the pressure screw
Cabel entry:
Seal 1+2+3
1 2
3
(Ø mm / Nm)
Seal 1+2
1 2
3
(Ø mm / Nm)
Seal 1
1 2
3
(Ø mm / Nm)
Test torque for screw in thread cable entry (Nm): 3.0
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
Terminals:
Test torque terminals:
Weight (standard version):
3- / 4-polig
PTB 99 ATEX 1164
6-pole
PTB 00 ATEX 1073
EN 60079-0
II 2 G Ex d e IIC T6
II 2 D Ex tD A21 IP66* T80 °C
IECEx BKI 07 .0005
IEC60079-0
Ex d e IIC T6
Ex tD A21 IP66* T53 °C
up to 690 V, 50/60 Hz
125 A
up to U
400 V up to U
N
200 A/gG
125 A
3-pole
2 x M63 + 1 x M25
4-pole
2 x M40
6-pole
4 x M63 + 1 x M25
M25
min.
8.0 / 1.5
(1)
max.
10.0 / 2.0
min.
10.0 / 2.3
(1)
max.
13.0 / 2.6
min.
13.5 / 1.3
(1)
max.
17 .5 / 2.3
3-pole
2 x 4.0 - 70 mm²
6-pole
6 x 95 mm²
max. 1 x 120 mm²
6.0 Nm
3-pole
ca. 16.00 kg
6-pole
ca. 31.00 kg
GB
500 V up to U
690 V
N
N
200 A/gG
160 A/gG
125 A
110 A
-
M40
M63
19.0 / 3.3
29.0 / 12.0
22.0 / 5.5
35.0 / 12.0
22.0 / 3.3
36.0 / 12.0
28.0 / 6.7
41.0 / 13.0
7 .5
7 .5
observe current load
(use cable lugs supplied with switches)

Publicité

Table des Matières
loading

Table des Matières