Auto bypass

Set the threshold of temperature of the switching map for heat exchange ventilation / bypass
ventilation.
Button operation
1
Commissioning menu
Initial setting
Airflow
Auto bypass
External input
Service
Main menu:
Cursor
F1
2
Outdoor temp. low limit
Target indoor temp.
Outdoor temp. cooler by
Select:
Cursor
F1
1/2
Page
F2
F3
F4
Auto bypass
Loading
Auto bypass
16
16
K
Temp
F2
F3
F4
Accessing the «Auto bypass» screen
Select "Auto bypass" from the Main menu >
Commissioning, and press the
The product data is loaded before the screen
will appear. [Loading] is displayed. (10 to 60
seconds)
The Auto bypass settings
Press the
and
Press the
and
value.
Press the
button to save the changes.
Eng-35
P
button.
button to move the cursor.
button to change the setting