What room temperature can you set?

Your universal controller offers 4 room operating
modes. Each operating mode are assigned 2
temperature setpoints (heating and cooling).
Your controller changes the setpoints according to
a time switch program, depending on the selected
room operating mode (
continuous operation to the setpoint of the se-
lected operating mode.
Symbol
Operating mode
Comfort
Precomfort
Economy
Protection
Siemens Building Technologies / HVAC Products
page 9), or provides
Impact on the room?
This is the operating mode for the occupied space. It ensures com-
fortable conditions
This is an energy-saving operating mode for the space to ensure that
comfortable conditions will be reached quickly when when changing
to Comfort mode
Plant OFF. A minimum / maximum temperature is ensured in the
space (unoccupied mode)
Plant OFF. Frost protection active
Welcome > Main menu > Controller 1... > ...
Path:
The following setpoints are available. The default values repre-
sent the recommended setpoints.
You can change the Comfort and Precomfort setpoints to suit
your individual needs.
CE1B3144x2
Guide value
Heating
21 °C
19 °C
16 °C
----
74 319 0350 0
Cooling
24 °C
28 °C
30 °C
----