Room temperature

Your universal controller offers 4 room operating modes.
Each room operating mode are assigned two tempera-
ture setpoints (heating and cooling).
Depending on the selected room operating mode, your
controller switches the setpoints per a time program
(
page 9) or controls continuously to the setpoint for
the selected room operating mode.
Symbol
Setpoint
Room operating
mode
Comfort
Precomfort
Economy
Protection
12
Building Technologies / HVAC Products
Impact on the room?
This is the setpoint for the occupied room.
Ensuring comfortable conditions
This is the energy saving setpoint for the room to ensure that com-
fortable conditions are reached quickly when changing to comfort
mode
Plant OFF. A maximum / minimum temperature is ensured in the
room (sustained mode)
Plant OFF. Frost protection active
Path: Welcome > Main menu > Controller 1... > ...
The following setpoints are available. The default factory
settings represent the recommended setpoints.
You can change the comfort and precomfort setpoints as
needed. The economy setpoint cannot be set at the user
level.
CE1B3144x2
Guide value
Heating
Cooling
21 °C
19 °C
15 °C
----
74 319 0350 0a
24 °C
28 °C
30 °C
----
31.01.2007