Putting into operation

6.1 Switching the appliance on and off
There are two methods to switch the appliance on or off.
1. Through software; the appliance remains connected to the
mains, when switching off bu software only the fans are
stopped.
2. Removing the mains plug or inserting it into the wall socket;
the voltage is taken from the appliance.
Switching on
• Mains power: connect the mains
plug to the electric installation
• Through
software;
simultane-
ously press keys "OK" and "+" to
switch on the appliance through
software
(Only possible after the appliance
has been switched off through
software.)
tes the position of the 3-way switch.
Switching off
• Through software; simultaneously
press keys "OK" and "-" to switch
on the appliance through software.
The text OFF appears on the dis-
play.
• Mains power: pull the mains plug
from the mains to take the voltage
from the appliance.
NOTE!
When working on the appliance, always take the voltage
and subsequently pulling the mains plug.
-
>3s
>3s
5383-0
Renovent HR Medium/Large
6.2 Setting the air quantity
The air quantity of the Renovent HR Medium/Large for settings
1, 2 and 2 have been adjusted in the factory at 100, /150/200
and 225/300 m
3
/h. The performance of the Renovent depends
stance.
Important:
Setting 1: must always be lower than setting 2.
Setting 2: must always be lower than setting 3;
Setting 3: adjustable between 50 and 300/400 m
If these conditions are not complied with, the air quantity of the
higher setting will automatically be adjusted.
here the air quantity for setting 3 will be changed from 300 to
3
280 m
/h):
1. Press key "F" during 3 seconds to
call up the settings menu.
2. Use key "+" to select the desired
parameter (U1 = setting 1: 1, U2 =
setting 2: 2, U3 = setting 3; U4, U5
and U8 only apply when a bypass
unit is used).
3. Press key "OK" during 1 second to
read the selected parameter value.
4. The keys "+" or "-" can be used to
modify the selected parameter va-
lue.
Chapter 6
-
3
/h;
>3s
17