Electrical Connection / Earthing; Terminal Strip Positionning For Star (Y) And Delta () Connection (Multi-Voltages Electric Motors); Lower Voltage :  Connection; Higher Voltage : Y Connection - salmson NEX Manuel D'installation Et Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

  ENGLISH  
 
 
 
Single mechanical seal with external quench :  
External piping system or raised tank should be installed in the state of 
the art. Pressure in the quench should not exceed 0,35 bar. 
 
Back to back mechanical seals :  
When  using  this  type  of  mechanical  seal  arrangement  the  use  of  a 
barrier  fluid  is  mandatory.  Compatibility  between  barrier  fluid  and 
pumped media should be confirmed. 
 If back to back pressurized mechanical seals are used : pressure in the 
auxiliary  system  will  be  set  at  2  bar  minimum  above  the  pressure 
calculated in mechanical seal chamber. Check that this pressure will not 
exceed max allowable pressure of MS on atmosphere side. 
When  high  temperature  fluid  is  pumped,  the  barrier  fluid  should 
 
circulate even when pump is off. 
 If back to back non pressurized mechanical seals are used : tank filled 
with the barrier fluid will be placed at a minimum height of 0,7 m above 
mechanical seal level. 
 
Tandem mechanical seals :  
Compatibility  between  barrier  fluid  and  pumped  media  should  be 
confirmed. 
 
After  pipe  work  is  done  turn  pump  shaft  by  hand  and  check  it  turns 
freely.  If  it  appears  that  it  is  difficult  to  turn  pump  shaft,  then  check 
forces applied by piping to pump casing. Positioning of piping should be 
done again. 
 
7.3 ELECTRICAL CONNECTION / EARTHING 
Check  that  motor  winding  corresponds  to  site  electric  power 
 
supply characteristics before electrical connections are performed. 
Connecting  a  230/400V  motor  on  a  400V  power  supply  or 
 
connection  of  a  400/690V  motor  on  a  690V  power  supply  might 
drive  to  motor  destruction  if  terminal  strip  are  positioned  in  a  wrong 
way. 
 
Electrical connection should be performed by qualified personnel 
 
only  having  necessary  agreements  and  in  compliance  with  local, 
national and international regulations. 
 
Equipments used in an ATEX zone will be connected in compliance 
 
with CEI60079‐14. It is the responsibility of the end user to select 
proper type and size of electric cable. 
 
Respect  motor  manufacturer  instructions  to  make  electric  motor 
 
connection (refer to the instructions supplied with the motor. they 
are  usually  indicated  inside  motor  junction  box).  Sensors  will  be 
connected  in  compliance  with  the  instructions  given  in  dedicated 
instruction manual. 
 
7.3.1
TERMINAL  STRIP  POSITIONNING  FOR  STAR  
(Y)  AND  DELTA  () CONNECTION  (MULTI‐
VOLTAGES ELECTRIC MOTORS) 
Multi‐voltage winding for voltages  230/400V and 400/690V :  
 
6 wiring terminals : 
To  change  motor  direction  of  rotation  reverse  two  phases  on  wiring 
terminals. Connection of earthing terminal is mandatory. 
 
7.3.2
Voltage : U 
 
7.3.3
Voltage : U3 
 
7.3.4
 
components  of  the  pumpset.  Each  part  of  the  pumpset  should  be 
connected  to  earth  with  a  correctly  calibrated  bonding  strap  or  cable 
(motor winding, motor frame, coupling guard, pump baseframe). 
 
7.4 USE OF A FREQUENCY INVERTER 
available and known. 
 
The  electric  motor  that  is  supplied  with  the  pump  may  be  connected 
under  conditions  to  a  VSD.  Variable  speed  will  be  used  to  reach  pump 
required duty point on site. To ensure a reliable use of the equipment a 
few precautions should be taken : 
 
Electrical requirements : 
  Variable  frequency  drive  will  not  generate  voltage  peak  higher  than 
850V  (motor phases isolation) and dU/dt values higher than 2500 V/µs 
(winding  isolation).  If  those  values  can  be  reached,  a  filter  should  be 
installed  :  ask  inverter  manufacturer  for  proper  selection  and  motor 
manufacturer for limit values. 
  Choose  a  vector  control  inverter  or  use  a  quadratic  V/F  control 
inverter. 
 Check that motor nominal voltage is never exceeded. 
 
 
Hydraulic requirements : 
 A dedicated suction pipe should be dedicated to each pump used with 
a negative suction head (suction lift). 
14 
LOWER VOLTAGE :  CONNECTION 
 
HIGHER VOLTAGE : Y CONNECTION 
 
Y /  STARTER : 
Grounding  of  the  complete  pumpset  will  be  performed  with 
special  care.  Earthing  will  avoid  any  electrostatic  accumulation  in 
When  pump  is  used  with  a  variable  speed  drive,  make  sure  that 
the  frequency  inverter  instructions  and  operating  manual  is 
Power supply cable should comply to ATEX regulation. Ensure that 
motor winding is equipped with CTP temperature sensors inside. 
A  physical  barrier  should  separate  power  supply  cables  and  low 
voltage cables to avoid analog signal distortion. 
 

Publicité

Chapitres

Table des Matières
loading

Table des Matières