6.3 ALARM TABLE

MESS. DISPLAY
DESCRIPTION
No water alarm -
A01
temporary
No water alarm -
A02
definitive
Pressure transducer
A03
alarm.

6.4 ERROR TABLE

MESS. DISPLAY
DESCRIPTION
E00
No event.
Fault generico.
E01
(segnalazione memoria)
Temporary external
E02
error.
Definitive external
E03
error.
E04
Communication error.
E05
Over voltage error.
Under voltage error
E06
temporary.
Under voltage error
E07
definitive.
Error due to the temporary absence of water.
This occurs when water is absent and the
restart mechanism has been activated. The will
wait before restarting in order to attempt to
automatically reset the error.
This condition occurs when there is no
water and the automatic restart system has
not activated or restart attempts occurred
already without managing to reset the system
functioning.
This alarm condition closes the J3 contact on
the power board for possible external signals
(alarm light, siren, etc.)
This signal occurs when the control board
cannot identify the transducer pressure signal.
The error log appears when no errors have been
signalled.
This error occurs in the presence of:
Internal module error
Overheating of the power module
Pump failure
An external error occurs when there is a problem
with the power module. The module will not be
operative during an EXTERNAL ERROR.
The definitive external error condition is
indicated after the temporary error condition is
repeated 5 times.
This error condition occurs when the control
board cannot communication with the power
part. This alarm condition closes the J3 contact
on the power board for possible external signals
(alarm light, siren, etc.).
This error occurs when the current absorbed
by the module is greater than triple the nominal
current.
This condition can be caused when the pump is
blocked by foreign bodies.
This alarm condition closes the J3 contact on
the power board for possible external signals
(alarm light, siren, etc.)
This error condition occurs when the voltage is
10% less than the nominal voltage (230V).
This alarm condition closes the J3 contact on
the power board for possible external signals
(alarm light, siren, etc.)
This error occurs when the temporary under
voltage condition is repeated 5 times.
ACTION
Check the water level in the first tank or the aqueduct
pressure. Wait for the programmed attempted restart
or press the button START/STOP for a manual restart.
Check the water level in the first tank or the aqueduct
pressure. Press the button START/STOP to manually
restart the system.
Check the pressure transducer is correctly connected.
If the error occurs again, contact your nearest
assistance centre.
ACTION
Press the START/STOP button to attempt to exit
this condition. In case of a persistent error, contact
technical support.
In this case, the module will attempt to restart normal
functioning after 5 minutes and will repeat this
procedure up to five times.
Press the START/STOP button to attempt to exit these
conditions. Please contact technical support of the
error persists.
Press the START/STOP button to attempt to exit this
condition. Please contact technical support of the
error persists.
Cut the power off and wait until the LINE Led switches
off and after which turn power back on. If the error
condition occurs again, contact your nearest assistance
centre.
Cut off the power supply and wait for the LINE Led
to switch off. Check the pump freely rotates and if
necessary remove foreign bodies that block correct
functioning.
Turn power back on.
If the error persists, contact your nearest assistance
centre.
Press the button START/STOP or cut the power off and
wait until the LINE Led switches off and after which
restart the system.
If the error occurs again, contact your nearest
assistance centre.