Before Each Use - Dri-Eaz PHD 200 Manuel Du Propriétaire

Masquer les pouces Voir aussi pour PHD 200:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

NOTICE: The unit is fitted with sensitive electronic sen-
sors. Protect the sensors and their lead wires from dam-
age and do not expose them to water or cleaning solu-
tion.
The following tools and supplies are needed to
complete the maintenance procedures described in
this manual:
Philips screwdriver
10 mm wrench
6 mm hex bit
¼ in. nut driver
Cleaning cloths
HEPA vacuum cleaner with soft brush nozzle and
crevice nozzle.
Recommended
Cordless drill, small knife, small-jaw pliers, coil clean-
ing solution, rotomolded housing cleaning solution.

Before each use

Inspect the electrical cord for damage. Look for fray-
ing, cuts, etc. Replace the cord if you find any damage.
Inspect filter. The PHD 200 filter should be replaced
when the accumulation of dust is visible.
Monthly
Inspect and clean coils and interior surfaces. In nor-
mal use, dust can accumulate and can restrict airflow,
reducing performance and causing the unit to overheat.
Clean when dust accumulation is visible. Remove grills
and cover as shown in Fig. B. Use a vacuum cleaner
with a brush tool and a soft cloth to remove any debris.
Take care not to damage any interior components.
To maintain appearance, wipe interior and exterior sur-
faces with a damp cloth. For deep cleaning and a last-
ing, protective shine, use an automotive interior cleaner.
07-01913C F515 2014-02 Warranty 07-01651
Fig. B: Disassembly for Cleaning
Remove the 4 screws
from housing and 2
top screws each from
inlet and outlet grills
and lift off cover.
As Needed
Clean pump check valve and basin. If the unit displays
the message "ER9 PUMP BLOCKED CHECK PUMP &
HOSE", the pump check valve and pump basin may
need to be cleaned. Remove grills and cover as shown
in Fig. B. Remove screws from pump base and lift out
pump. Wipe out pump basin with a damp cloth. Unthread
barbed fitting with check valve and rinse fitting and
check valve with clean water. Reinstall barbed fitting into
pump. Do not overtighten. Reinstall pump on base. Re-
install cover and grills.
Clean coils. With the cover removed, inspect both coils.
If excessive dust and debris is present, vacuum thor-
oughly and/or clean with coil cleaner.
5