6. Technical specifications

HV MODEL (400V)
CAPACITY*
INPUT
Voltage
Low Line Loss
Range
Low Line
Comeback
High Line Loss
High Line
Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Phase
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Over
AC mode
load
Battery mode
Current Crest Ratio
Harmonic Distortion
Transfer
Line
Battery
Time
Inverter
Bypass
Inverter
ECO
EFFICIENCY
AC mode
Battery Mode
BATTERY
Standard
Type
Model
Numbers
Recharge Time
Charging Current
(max)
Charging Voltage
Long-run
Type
Model
Numbers
Charging
Current(max.)
Charging Voltage
PHYSICAL
Standard
Dimension, D X W
Model
X H (mm)
Net Weight (kgs)
Long-run
Dimension, D X W
Model
X H mm
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
102
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 07 19 AA 59 205 03
E4
E4
Evolution
Evolution
II + 10 k
II + 15 k
TT (S)
TT (S)
10KVA /
15KVA /
10KW
15KW
110 VAC(Ph-N) ± 3 % at 50% Load; 176 VAC(Ph-N) ± 3 % at 100% Load
300 VAC(L-N) ± 3 % at 50% Load; 276 VAC(L-N) ± 3 % at 100% Load
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
12 V / 7 Ah
12 V / 9 Ah
20 (10+10)
32 (16+16)
9 hours recover to 90% capacity
2.0 A ± 10% (Recommended)
1.0~12.0A (Adjustable)
+/-136.5
VDC ± 1%
20
1.0~12.0A ±10% (Adjustable)
+/-136.5
VDC ± 1%
626 x 250 x 750
124/126
139/141
626 x 250 x 750
28/30
43/45
0 ~ 40°C (the battery life will down when > 25°C)
E4
E4
Evolution
Evolution
II + 20 k
II + 30 k
TT (S)
TT (S)
20KVA /
30KVA /
20KW
30KW
Low Line Loss Voltage + 10V
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
3 Phase with Neutral
≧ 0.99 at 100% Load
3 Phase with Neutral
360/380/400/415VAC (Ph-Ph)
208*/220/230/240VAC (Ph-N)
± 1%
46Hz ~ 54 Hz @ 50Hz system;
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
3:1 max
0 ms
<10 ms
95.5%
94.5%
12 V / 9 Ah
12 V / 7 Ah
32 (16+16)
(16+16)pcs x 2 strings
+/-218 VDC ± 1%
Depending on applications
32 ~ 40 (adjustable)
+/- 13.65 VDC * N ± 1% (N = 16~20)
815 x 300 x 1000
139/141
225/230
815 x 300 x 1000
43/45
60/65
<95 % and non-condensing
<1000m**
E4
E4
Evolution
Evolution
II + 40 k
II + 60 k
TT (S)
TT S
40KVA /
60KVA /
40KW
60KW
12 V / 9 Ah
N/A
2.0~24.0A ±10%
(Adjustable)
N/A
250/260
790 x 360 x 1010
61/71
108/112
E4
Evolution
II + 80 k TT
S
80KVA /
80KW
113/117