Siemens 6DR50.1-0N Notice De Service page 39

Positionneurs électropneumatiques
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Construction
Manometer, steel
Manometer made of stainless steel 316
Vibration resistance
Connections, electrical
Screw terminals
Cable gland
Connections, pneumatic
7.1.4
Controller
Controller
Control unit
Five-point controller
Dead zone
dEbA = auto
dEbA = 0.1 ... 10 %
Analog-to-digital converter
Scanning time
Resolution
Transmission error
Temperature influence
SIPART PS2 (6DR5...)
A5E03436620-06, 04/2015
IP44
IP54
In accordance with DIN EN 837-1
2.5 mm
AWG30-14
2
Without Ex protection as well as with Ex i: M20x1.5 or ½-
14 NPT
With explosion protection Ex d: Ex d certified M20x1.5, ½-
14 NPT or M25x1.5
Female thread G¼ or ¼-18 NPT
Adaptive
Adaptive
Can be set as fixed value
10 ms
≤ 0,05 %
≤ 0,2 %
≤ 0.1 %/10 K (≤ 0.1 %/18 °F)
41

Publicité

Table des Matières
loading