2. Use the
button to change from linear actuator to part-turn actuator until the display shows the following:
3. Call the "2.YAGL" parameter. To do this, briefly press the
automatically. The display shows the following:
4. Call the "4.INITA" parameter. To do this, briefly press the
5. Start the initialization process. To do this, press the
following:
The positioner runs through five initialization steps during the automatic initialization process. Displays for the
initialization steps from "RUN1" to "RUN5" are shown in the lower line on the display. The initialization process depends
on the actuator used, and takes up to 15 minutes.
6. The following display indicates that the automatic initialization is complete. The total angle of rotation of the actuator is
shown on the upper line on the display:
Aborting the automatic initialization process
1. Press the
button. The display shows the following:
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
The software status is displayed.
After releasing the
34
button, the positioner is in "P manual mode". The part-turn actuator is not initialized.
button. This parameter has already been set to 90°
button. The display shows the following:
button for at least 5 seconds until the display shows the
button for at least 5 seconds.