CONTROL FUNCTIONS

Protective functions

Compressors stops when:
– High pressure exceeds 108 bar.
– Restarts with manual reset.
– Low pressure is below 15 bar.
– Automatic reset.
– BLDC Power + Alarm. See display information. Compressor
auto reset.
– 5 times before alarm becomes manual.
– Compressor out of envelope alarm. Compressor auto reset.
– 5 times before alarm becomes manual.
EC Gas cooler fan is protected by internal temperature sensor.
– Automatic reset.
All alarms are visible after pressing the flashing red warning triangle.
Hold down to reset. Example here:
disconnected.
Alarm list
A complete list of controller alarms can be found on appendix 2.
suction pressure probe broken or