SCOPE OF APPLICATION

Produit
Compressor model
R efrigerant
O il(Supplier)
A lternative oi l
Evaporating
temp erature
Suction
Cir cuit du
superheating
fluide
Discharge gas
f rigorigè ne
temperature
Inverter
operation
Nominal
Revolution
T emperature
Ambient
Relative
Humidity
Allow ed fluids
W ater cir cuit
W ater inlet
(wa ter c ooled
temp erature
versio n)
Water mass
flow
Pressure drop
(wa ter side)
On/off cycle period
L iquid line temperature stand ard
re ceiver pressure settings
* Depending on the ambient temperature the use of the Polar kit should follow the following recommendations:
Ambient Temperature < -15°C Mandatory
Ambient Temperature < +5°C Recommended
QC
QC
30MT
45MT
R744
P AG VG100S
PAG100 FUCHS
-18°C à +5°C
20K or below
+ 120°C or below
25–100 tr/s
70 rps
-15°C* / + 43°C (the ambient temperature can be -30°C if polar kit hea ter is
installed)
10% – 90%
W ater, Water-glycol (MPG / MEG – 60% maxi)
-8°C to 35°C (nominal +7°C / +12°C)
V ariable (depend on the capacity)
50 kPa or below
5 min or longer for on/off cycles
55 Bar (19°C)
QUIETCO
OL serie
2
Toshiba
QC
QC
67MT
100MT
10
QC
QC
112LT
75LT
-32°C à -18°C
45–100 tr/s (LT)
25-100 tr/s (MT)
35 Bar (0°C)
QC
167 LT