OPERATING

Do not use other than the designated refrigerant (for charging, adding or recharging).
Do not use the refrigeration equipment or components for any utilization other than
that for which it is designed.
Comply with the special manufacturers recommendations contained in the
manufacturers operating instructions.
It is strictly prohibited while the device is running to remove the guards and
panelling provided by the manufacturer to protect the user and ensure his safety.
When operating, surface temperatures above 60°C and /or below 0°C may be
reached. During any servicing operation, the personnel should be extremely careful
while working on the device.
The manufacturer is not informed to real use of partly completed machines; their
integrations and use must comply with Machines Directive and recommendations of
these operating instructions.
Results of design calculations, checks, and test reports in relation with low voltage
directive are archived.
Water cooled QUIETCO
The cooling fluid of the Water Cooled QUIETCO2OL must either be water or a
mixture of water and MEG or water and MPG (maximum MEG/MPG concentration:
60%).
The inlet temperature of this fluid must be in a -8°C/+35°C range. The nominal
range is between +7°C and +12°C.
The water circuit is equipped with a three way valve which allows regulating the by-
pass of the gascooler.
A thermostatic control valve allows controlling the water flow which passes through
the intercooler on the LT versions. This valve operates by measuring the temperature
of the refrigerant on the CO2 outlet of the heat exchanger.
When dimensioning the water circuit, the installer must take into account the
pressure losses of the water pipes and the exchanger(s).
The
hydraulic
OL features
2
circuit
thermal
insulation
20
is
proposed
in
option