LEGRAND DAKER DK Plus 5 kVA Manuel D'installation page 72

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Efficiency
Overload capacity
Number of output
phases
Battery charger characteristics
Rated Battery
Voltage
Maximum charge
current
Recharge time
(to 90%)
Communication and management
Screen and signalling
Communications ports
Software
Protections
Mechanical characteristics
Dimensions
W x H x D( mm)
Net weight (kg)
Environmental conditions
Operating
temperature
Operating relative
humidity
72
3 101 75
3 101 76
120% for 30 seconds
150% for 10 seconds
six pushbuttons and four LEDs for real-time control
of the status and the main parameters of the UPS
Connector for network interface
Software for Windows and Linux environments
is available in order to:
- displaying all the functioning and diagnostic
data in case of problems;
- setup of special functions.
Download a copy free of charge from the website
http://www.ups.legrand.com
Electronic circuits against overloads and short-circuit
Emergency Power Off (EPO)
440 x 88 (2U) x 680
25
20% to 80% (non-condensing)
7 Technical specifications
3 101 77
up to 94%
105% continuous
Single phase
240 Vdc
1.86 Adc
4 hours
RS232 and USB
Backfeed
Overtemperature
440 x 132 (3U) x 680
0 ºC to +40 ºC
+32 ºF to +104 ºF
3 101 78