OPERA
Legend
139
Remote Control: it can be installed in place of 72 to manage the request of the 1st zone (direct)
300
Burner On indication (voltage-free output): the example shows the connection of an hour counter at 230Vac
301
Fault indication (voltage-free contact output): the example shows the connection of a lamp at 230Vac
302
Remote reset input (230Vac): the example shows the connection of a double-pole switch at 230Vac, allowing the resetting of a
block type fault
357
Fault indication (230Vac): the example shows the connection of a lamp at 230Vac
Two mixed heating circuits, one direct heating circuit and one DHW circuit with circulating pump
- Schematic diagram
The FZ4B zone control board can manage different types of systems. An example is given.
Use diverter valves with 3 wires:
- 230V OPENING PHASE
- 230V CLOSING PHASE
- NEUTRAL
with switching times (from all closed to all open) of not more than 180 seconds.