#17 = N.O. Relay Output
#16 = N.O. Relay Output
#30 = 0–10 VDC Output
#2 = Analog Common
1 2 5 6
1 2 5 6
U/T1
V/T2
Terminals 2 and 16 are tied
together on the first VFD.
The motor wiring configurations shown below are applicable to 9-lead, dual voltage, wye wound motors rated
for 230/460 VAC and 330/600 VAC. Consult the motor nameplate and/or wiring placard for verification of
required wiring connections. Jumper bars are provided with the motor. Motors with terminal blocks require ring
terminals and a 7 mm nut driver for termination. The diagrams below include T2 and T3 swap to yield proper
motor rotation. Swapping leads to reverse rotation is done only on the output side of the drive.
200–240 VAC, 50–60 Hz
330–350 VAC, 50–60 Hz
U2
T4
U5
T7
U1
T1
WHITE
RED
BLACK
GREEN W/ YELLOW TRACER
34
25 4 11
25 4 11
13A 13B 13C 14 30 16 17
13A 13B 13C 14 30 16 17
PE
W/T3
L1
L2
L3
WHITE
BLACK
RED
MOTOR WIRING
Low Voltage
V2
W2
T5
T6
V5
W5
T9
T8
V1
W1
T3
T2
WWW.BIGASSFANS.COM
#4 = Digital Common
#5 = 0–10 VDC Input
#2 = Analog Common
#1 = Run/Stop Input
Terminals 2, 4, and 16
are tied together on all
downstream VFDs.
3 Conductor Shielded Cable
Minimum 20 AWG Stranded (Installer-Supplied)
Recommended Max Distance = 200 ft (61 m)
WHITE
RED
BLACK
GREEN W/ YELLOW TRACER
© 2018 DELTA T LLC
ALL RIGHTS RESERVED.
#17 = N.O. Relay Output
#16 = N.O. Relay
Output
#30 = 0–10 VDC
Output
1 2 5 6
1 2 5 6
25 4 11
25 4 11
13A 13B 13C 14 30 16 17
13A 13B 13C 14 30 16 17
PE
L1
L2
L3
U/T1
V/T2
W/T3
WHITE
WHITE
BLACK
BLACK
RED
RED
High Voltage
400–480 VAC, 50–60 Hz
575–600 VAC, 50–60 Hz
V2
U2
T4
T5
V5
U5
T8
T7
U1
V1
T1
T2
0–10 VDC and Start/
Stop Out to Next
Downstream VFD
W2
T6
W5
T9
W1
T3