Class 4 Status Codes - Fronius Galvo 208-240 Instructions De Service

Masquer les pouces Voir aussi pour Galvo 208-240:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code
Description
LOW PV POWER
Intermediate circuit voltage
306
has dropped below permissible
threshold value for grid power
feed operation.
LOW PV VOLTAGE
DC input voltage has dropped
307
below permissible threshold
value for grid power feed oper-
ation.
IMPORTANT! Status codes 306 (LOW PV POWER) and 307 (LOW PV VOLTAGE) appear naturally every
morning and evening due to low solar irradiance. These status codes are not the result of a fault.
308
Intermediate circuit overvolt-
age
309
DC input voltage too high
Class 4 Status
Class 4 status codes may require the intervention of a trained Fronius service technician.
Codes
Code
Description
No internal communication
401
with power stage set.
Power stage set temperature
406
sensor defective
Internal temperature sensor
407
defective
408
DC feed-in detected
The "fixed voltage" setting has
been selected instead of MPP
412
voltage operation and the volt-
age is set to a value that is too
low or too high.
Safety cut-out has been trig-
415
gered by option card or RE-
CERBO
No communication between
416
power stage set and control
unit
Communication with the power
425
stage set is not possible
Limit value setting not permit-
445
ted
Neutral conductor not connect-
448
ed
44
Details
Brief interruption of grid power
feed operation.
The inverter returns to the
Startup phase.
Brief interruption of grid power
feed operation.
The inverter returns to the
Startup phase.
Details
The inverter will automatically
attempt to connect again and,
if possible, resume grid power
feed operation.
-
Inverter does not feed energy
into the grid.
The inverter will automatically
attempt to connect again and,
if possible, resume grid power
feed operation.
Inverter does not feed energy
into the grid for safety reasons.
Rectification
The fault is rectified automati-
cally.
If this status code keeps recur-
ring with sufficient solar irradi-
ance, contact your system
installer.
Error is automatically rectified;
if status code persists: contact
a Fronius-trained service tech-
nician.
Rectification
If status code persists: contact
a Fronius-trained service tech-
nician.
If this status code keeps recur-
ring, contact your system in-
staller.
If status code persists: contact
a Fronius-trained service tech-
nician.
Update the inverter firmware.
If status code persists: contact
a Fronius-trained service tech-
nician.
If this status code keeps recur-
ring, contact your system in-
staller.

Publicité

Table des Matières
loading

Table des Matières