Version - Fronius Galvo 208-240 Instructions De Service

Masquer les pouces Voir aussi pour Galvo 208-240:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

AC Voltage Derating:
Fault Ride Through:

Version

Display of version number and serial number of the PC boards installed in the inverter (e.g.,
for service purposes)
Display range
Status
ON / OFF voltage-dependent power reduction
GVDPRe
Threshold from which the voltage-dependent power reduction
begins
GVDPRv
Reduction gradient used to reduce the power, e.g.: 10% per volt
above the GVDPRe threshold.
Message
Activates the dispatch of an info message via Fronius Solar Net
Status – default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately when a short-term interruption to the AC voltage oc-
curs (outside of the limits set by the grid supplier); instead it
continues to supply power for a defined time.
DB min – default setting: 90%
"Dead Band Minimum" setting (%)
DB max – default setting: 120%
"Dead Band Maximum" setting (%)
k-Fac. default setting: 0
Display/Display Software/Integrity Checksum/Memory Card/
Memory Card #1/Power Stage/Power Stage Software/EMI Fil-
ter/Power Stage #3/Power Stage #4
35