Fan; Arc Detection - Fronius Galvo 208-240 Instructions De Service

Masquer les pouces Voir aussi pour Galvo 208-240:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fan

for checking the fan functionality
Setting range
-
-
-

Arc Detection

for checking arc detection/interruption
Setting range
Arc.det. Status
displays the current status of arc detection/interruption
Start Self-test
self-test to check whether the inverter interrupts grid power feed operation when an arc
is detected.
Test procedure:
The self-test starts. The arc detection/interruption function simulates an arc and sends
the corresponding signal to the inverter.
If the test is successful, the inverter disconnects from the grid and stops grid power feed
operation.
The message "Self-test completed and Start AFCI" is shown on the display.
32
Use the "Up" and "Down" keys to select the desired fan
Press the "Enter" key to start testing the selected fan
The fan runs until the menu is exited by pressing the "Esc" key
Select "Arc Detection" in the Setup menu
1
Press the "Enter" key
2
Use the up and down keys to select "Start Self-test"
3
Press the "Enter" key
4
Confirm the indication by pressing the "Enter" key
5
Test fan 1 / Test fan 2 (depends on device)
ArcDetector Status/Start Self-test

Publicité

Table des Matières
loading

Table des Matières