Status Diagnosis And Troubleshooting; Displaying Status Codes; Total Failure Of The Display; Class 1 Status Codes - Fronius Galvo 208-240 Instructions De Service

Masquer les pouces Voir aussi pour Galvo 208-240:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Status Diagnosis and Troubleshooting

Displaying Sta-
Your inverter is equipped with a self diagnostic system that automatically identifies a large
tus Codes
number of possible operation issues by itself and displays them on the screen. This en-
ables you to know immediately if there are any malfunctions in the inverter, the photovoltaic
system or any installation or operating errors.
Whenever the self diagnostic system has identified a particular issue, the respective status
code is shown on the screen.
IMPORTANT! Status codes may sometimes appear briefly as a result of the control re-
sponse from the inverter. If it subsequently continues to operate normally, there has not
been a system error.
Total Failure of
If the display remains dark for a long time after sunrise:
the Display
-
Class 1 Status
Status codes in class 1 are typically temporary. Their cause lies in the grid.
Codes
Your inverter's first reaction is to disconnect from the grid. Thereafter, the grid will be
checked for the duration of the observation period stipulated. If, after the end of this period,
no further defect is identified, your inverter resumes grid power feed operation.
Code
Description
102
AC voltage too high
103
AC voltage too low
105
AC frequency too high
106
AC frequency too low
107
AC grid outside of tolerances
108
Stand alone operation detect-
ed
Class 2 Status
Codes
Code
Description
212
Overvoltage at L1-N
213
Undervoltage at L1-N
222
Overvoltage at L2-N
223
Undervoltage at L2-N
240
Arc detected
42
check the AC voltage at the inverter's connections:
the AC voltage must be 208–240 V (+10% / -12%) according to the grid.
Details
Grid conditions are being test-
ed and as soon as they are
back within the permissible
range, the inverter will resume
grid power feed operation.
Details
Grid conditions are being test-
ed and as soon as they are
back within the permissible
range, the inverter will resume
grid power feed operation.
The status code is displayed
for approx. 4 seconds.
Rectification
Check grid connections.
If this status code keeps recur-
ring, contact your system in-
staller.
Rectification
Check grid connections. If this
status code keeps recurring,
contact your system installer.
-

Publicité

Table des Matières
loading

Table des Matières