Dometic MCS6 Notice D'utilisation page 21

Masquer les pouces Voir aussi pour MCS6:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 75
MCS6, MCS12, MCS16
P-13: Reverse Automatic Fan Speeds During Heating
The automatic fan speeds can be reversed during Heating Mode. The fan will
speed up as the set point is approached. Lowering the fan speed when the
cabin is cold increases head pressure and helps raise supply temperature.
The fan switches to low speed when the set point is satisfied and the com-
pressor cycles off.
Normal fan operation is represented by "nor".
➤ To reverse fan speeds in heating, select "rEF".
P-14: Cycle Fan with Compressor
The fan can be programmed to run continuously when the system is on or
can be allowed to cycle with the compressor.
The default is "con", continuous fan.
➤ To cycle the fan with the compressor select "CYC".
NOTE
I
When used with optional electric heat the fan will remain on 4 min
after the heater cycles off.
P-15: Reverse Cycle or Electric Heat
➤ Do not change the default parameter.
P-16: Fan Motor Selection
NOTE
I
The unit's High Velocity (HV) blower has a Split Capacitor (SC) fan
motor. For this motor this parameter must be changed from "SP" to
"SC" in order for the blower to work at peak efficiency.
➤ Select "SC".
➤ Save this change as a new default by simultaneously pressing and releas-
ing the Up and Down Buttons prior to exiting the program mode.
➤ Make note of new default in the Programmable Parameters table for
future reference and servicing.
EN
Programming
21

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mcs12Mcs16

Table des Matières