Standard mechanisms of the PROFIBUS DP are used to transport
diagnostic information. The DIAGNOSIS parameter from the Physical
Block is then available to the master as diagnostic information. The
diagnostic messages can be made visible online in the module status
with the aid of a tool, e.g. SIMATIC HW config (STEP 7).
A diagnostic telegram is sent in place of the cyclic measured value
when a diagnostic message comes or goes. The diagnosis can be read
out on a class 1 master if the station is switched "online" (station is the
hierarchical stage beneath a project in the SIMATIC Manager, see
section 6.4 "Literature and Catalogs" /2/):
under module status
S
in the DP-Slave diagnostics register
S
The SIPAN 32 PA supplies diagnostics data in the following form:
Input (master view): diagnostics according to PROFIBUS-DP
Start address
1) Specifier:
1: Error appears
2: Error disappears
(DDLM_Slave_Diag)
0
Station_status_1
1
Station_status_2
2
Station_status_3
3
Diag_Master_Add
4
Ident_Number
5
Ident_Number
6
Header
7
Status_Type
8
Slot_Number
1)
9
Specifier
10
Diagnosis (0)
11
Diagnosis (1)
12
Diagnosis (2)
13
Diagnosis (3)
Dispositif de mesure de conductivité SIPAN 32
Standard DP diagnostics
Status coding according
to DP/V1
(quality indicator)
Diagnostic object of the
physical block