LOGIC ADJUSTMENTS
TRIMMER
T.L.
Work Time adjustment: from approx. 5 to 240 seconds;
T.C.A.
Automatic Closing Time adjustment: from approx. 5 to 120 seconds
(see dip switch 1);
FR.
obstacle detection sensitivity adjustment (only for motors with encoder).
Note: turn the TRIMMER clockwise to increase adjustments; turn it anti-
clockwise to decrease.
Dip switches
after opening, the gate automatically closes when the delay set on the T.C.A. trimmer
1 On
expires;
Off
a command is required to close the gate;
with automatic closing enabled, a sequence of open/close commands causes the gate
2 On
to OPEN-CLOSE-OPEN-CLOSE etc.;
in the same conditions, the same command sequence causes the gate to OPEN-
Off
STOP-CLOSE-STOP-OPEN-STOP (step-by-step) (see also dip switch 9);
Man Present; the automation system will continue to open or close as long as the
3 On
OPEN or CLOSE buttons are held down. The gear motor will stop when the button is
released;
normal (or pulse); when the OPEN, CLOSE or the PP button is pushed, the automatic
Off
system performs a complete opening or closing manoeuvre;
Note: in the Man Present mode, the PP input (n° 13) is disabled, as is the radio receiver.
4 not used;
5 On
encoder disabled (obligatory if the motor is not fitted with an encoder);
Off
encoder enabled (only for motors with encoder);
6 On
pre-flashing and "photocell test" function enabled;
Off
pre-flashing and "photocell test" function disabled;
after the photocell contact triggers (input 16 - 18), the automation system closes after
7 On
5 seconds;
Off
function disabled;
8 On
the gate works as set by dip switch 2
Off
the gate ignores the close command during the opening cycle;
during opening, the photocell cuts in to stop the gate until the obstacle is removed.
9 On
During closing, it stops the gate and then totally reopens it.
during opening, the photocell does not trigger while during closing, it behaves as if the
Off
dip switch were on;
10 On
braking enabled;
Off
braking disabled;
Note: the braking system activates whenever the motor must stop (FCC - FCA - STOP –
change of direction) and reduces the inertia accumulated by the gear motor during
movement.
Clock function:
A timer can be connected to the open-close pushbutton in order to keep the gate open at certain
times during the day, after which it reverts to automatic closing.