SDMO AT206 Manuel D'utilisation page 42

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
Switch (check the type fitted
in the control unit)
Type
BF9T
BF12T
BF18T
BF26T
BF38T
BF40
BF50
BF65
BF80
CL04
If the guidelines set out in this manual are not respected during installation of the equipment, it may
compromise both the operation and service life of the control unit and the product warranty.
Thermal current Ith of the
remote control switch
25A
45A
56A
60A
Minimum and maximum
section of flexible cable
connected without terminals
mm
1-6
1-6
1-6
2.5-6
2.5-16
2.5-16
4-50
4-50
6-50
2.5-16
POWER CONVERSION TABLE
Maximum flow of the control unit
400V AC 3P+N
kVA max / I max
17kVA / 25A
31kVA / 45A
38kVA / 56A
42kVA / 60A
Minimum and maximum tightening torque of the terminals.
During connection of the power cables,
take care not to remove the auxiliary
cables and ensure that these are
correctly tightened together with the
power cable.
Nm
1.5-1.8
1.5-1.8
1.5-1.8
2.5-3
2.5-3
2
4-5
4-5
4-5
1.4
Maximum flow of the control
unit
230VAC 3P+N
kVA max / I max
10kVA / 25A
18kVA / 45A
22kVA / 56A
24kVA / 60A
8 / 32
Ibft
1.1-1.5
1.1-1.5
1.1-1.5
1.8-2.2
1.8-2.2
2.24-2.88
2.95-3.69
2.95-3.69
2.95-3.69
1.02
Maximum flow of the control
unit
230Vac 1P+N
kVA max / I max
9kVA / 40A
16kVA / 72A
20kVA / 89.5A
22kVA / 96A