en - Original instructions
Pa-
Description
Range
ra-
me-
ter
1=invert the di-
rection of rota-
tion
dP
This parameter
0–99
is the value for
starting the
pump after a
stop, calculated
as a percent-
age of the re-
quired set point
value. Exam-
ple: SET
PRESS =
4.0bar dP =
90% (3.6 bar).
If the pressure
in the system
reaches the re-
quired pressure
of 4.0 bar and
there is no ad-
ditional con-
sumption, the
converter disa-
bles the pump.
As consump-
tion increases
and the pres-
sure decreas-
es, the convert-
er turns on the
pump when the
pressure falls
below the dP
value of 3.6
bar.
WARNING:
If the parameter EL=0 and MP=0, the
pump is not protected against dry run-
ning. The warranty does not cover dam-
age to the electric pump caused by in-
correct configuration.
• For motor cables longer than 30 m, it may be
necessary to increase motor current by 10%.
Check this in relation to the type of installation
and cable.
– Example: In=5A, set the parameter at 5.5A.
Table 18: Models MMA and MTA
Param-
Description
eter
LAN-
Language se-
GUAGE
lection
13
Imax: maximum current supplied. The value varies according to the model of converter.
36
Unit of
Default
meas-
urement
%
90
Range Unit of
Default
meas-
ure-
ment
ITAL-
-
ITAL-
IAN
IAN
Param-
Description
eter
NOM.C
Set the cur-
URR
rent rating
value of the
pump motor
on the data
plate.
ROTA-
For three-
TION
phase motors,
invert the di-
rection of ro-
tation.
0=no action
1=invert the
direction of
rotation
MIN.FR
Minimum
EQ
start-up and
stop frequen-
cy of the mo-
tor. Frequen-
cy at which
the converter
begins to run
(upon start-up
and shut-
down) without
using the
ramps.
EXT.LO
Enable the
W WA-
digital input
TER
and connect
the level sen-
sor to ensure
that the pump
stops when
there is no
water. See
(refer to figure
5.7). Alarm
Range Unit of
Default
meas-
ure-
ment
ENG-
LISH
GER-
MAN
FRENC
H
SPAN-
ISH
DUTCH
POR-
TU-
GUESE
POL-
ISH
TURK-
ISH
GREEK
13
0.1–6.0
Ampere Imax
(MMA0
6)
0.1–
12.0
(MMA1
2)
0 / 1
-
0
15–45,
Hz
30
three-
phase
motor
20–45,
single-
phase
motor
NO:
-
NO
Disa-
bled, no
control
YES:
Ena-
bled