Mixer module parameter settings

Parameters
Setting range
Min / Max
Min. mixer
10 - 100%
valve pump
Max. mixer
20 – 100%
valve pump
Slope offset
0 - 50 K
Mixer temper-
0 – 100 °C
ature, current
Mixer temper-
0 – 90 °C
ature, target
Mixer pump
On
status
Off
PWM mixer
0 – 100%
pump
Mixer valve
Neutral
status
Closed
Open
Tab. 9-2
Parameters of the mixer module
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Description
[→ Main menu → System]
Minimum power of the pump in the mixer circuit.
[→ Main menu → System]
Maximum power of the pump in the mixer circuit.
[→ Main menu → Heating]
Setting of the slope offset of the feed target temperature on the Daikin
Altherma EHS(X/H) in comparison with the feed target temperature determ-
ined for the mixer circuit.
[→ Main menu → Information → Values]
Current feed temperature in the mixer circuit
[→ Main menu → Information → Values]
Current target feed temperature in the mixer circuit
[→ Main menu → Information → Values]
Current status of the mixer pump
[→ Main menu → Information → Values]
Current modulation of the mixer pump
[→ Main menu → Information → Values]
Current status of the mixer valve
The parameters available for the mixer module are largely identical
to the parameter described in
Chap.
parameters available for the mixer module.
9
Mixer module
7.
Tab. 9-2
lists the additional
Factory
Incre-
Access
setting
ment
BE HF
30%
1%
N
E
100%
1%
N
E
5 K
1 K
N
E
-
-
S
S
-
-
S
S
-
-
S
S
-
-
S
S
-
-
S
S