7.6

Configuration

[→ Main menu → Configuration]
7.6.1

Menu: Sensors

[→ Main menu → Configuration → Sensors]
Parameters
Setting range
Min / Max
Outside tem-
Integrated sensor Selection of whether the sensor integrated in the outdoor unit or an optional
perature
Optional sensor
sensor (*)
Tank temper-
ature sensor
Inactive
Sensor
Thermostat
Water pres-
sure sensor
Off
On
Adjustment
-5.0 - +5.0 K
outside tem-
perature
Water pres-
0.1 - 5.0 bar
sure min.
Water pres-
0.1 - 5.0 bar
sure max.
Water pres-
0.1 - 5.0 bar
sure target
Max. pressure
0.1 - 5.0 bar
drop
Tab. 7-20 Parameter in menu: "Sensors"
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Description
outside temperature sensor is used to determine the target feed temperat-
ures
Configuration of the domestic hot water preparation:
No function for domestic hot water preparation.
Function for domestic hot water preparation is activated. A storage temper-
ature sensor is evaluated for domestic hot water preparation (if no storage
temperature sensor is connected, an error message is generated).
Function for domestic hot water preparation is activated. A thermostatic
switch (ON/OFF) is evaluated for domestic hot water preparation, where an
"open terminal" is evaluated as "not required".
Configuration of the sensor for detecting the water pressure of the system.
No sensor evaluation
Sensor evaluation activated (if no pressure sensor is connected, an error
message is generated.)
Individual adjustment for the measured value of the outside temperature
relevant for the control unit.
Defines the minimum water pressure.
Pressure monitor function (only with activated pressure sensor, [Water
pressure sensor]=On): If the measured value undercuts the set value, the
Daikin Altherma EHS(X/H) is shut off and an error message is generated.
Defines the maximum water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor]=On): If the measured value exceeds the set value, a
warning message is generated.
Defines the target water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = on): If the measured value undercuts the value set in
the [Maximum pressure loss] parameter, a warning message is generated.
Defines the maximum acceptable pressure loss in the heating system.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor]=On): If the measured value undercuts the value set in the
[Water pressure target] parameter by more than the set value, a warning
message is generated.
7
Parameter settings
Factory
Incre-
Access
setting
ment
BE HF
-
N
-
N
-
N
0.0 K
0.1 K
N
0.5 bar
0.1 bar
N
3.0 bar
0.1 bar
N
0.9 bar
0.1 bar
N
0.5 bar
0.1 bar
N
Operating Instructions
E
E
E
E
E
E
E
E
39