  • FRANÇAIS, page 115
7
Parameter settings
Parameters
Setting range
Min / Max
Circulation
pump control
Off
1 - 15 min
Thermal disin-
fection day
Off
Monday
...
Sunday
Daily
Thermal disin-
00:00 - 23:45
fection start
time
Thermal disin-
60 – 70 °C
fection temp.
Tab. 7-24 Parameter in menu: "Hot water"
7.6.6

Menu: Additional programs

[→ Main menu → Configuration → Addition]
Parameters
Setting range
Min / Max
Relay Test
Output J1
Output J14
Output J2 contact
A
Output J2 contact
B
Output J12 3UV
DHW open
Output J12 3UV
DHW closed
Connection J3 N/
O contact B
Connec. J3
changeover con-
tact A
Output J10
Output J17 relay
K2
Output J17 relay
K1
Output J17 relay
K3
Air Purge
Off
On
Operating Instructions
44
Description
Setting of the interval control for an optional circulation pump. Use in
France not permitted!
Deactivated.The circulation pump runs permanently during the release
times of the assigned switching time program ([Circulation pump control]
parameter).
The circulation pump runs clocked (clock cycle ratio: pump runtime = set-
ting value each 15 min).
Setting of the day for thermal disinfection of the hot water storage tank.
No thermal disinfection
Day of thermal disinfection
Daily thermal disinfection
Setting of the start time for thermal disinfection of the hot water storage
tank (format hh:mm).
Setting of the hot water target temperature during thermal disinfection of
the hot water storage tank.
Description
Manual control of individual relays for test purposes. After confirmation of
this parameter with the rotary button, the list of relays 1 - 9 is displayed with
a checkbox on the display. For selection and confirmation of a relay with
the rotary button, a tick is placed in the checkbox and the respective relay
is activated. Multiple selection is possible.
Output J1 (internal heating circulation pump), output pump
Output J14 (circulation pump), mixer "Open"
Contact A on output J2 (3UVB1 switching valve), mixer "Closed"
Contact B on output J2 (3UVB1 switching valve)
Output J12, 3UV DHW switching valve "Closed"
Output J12, 3UV DHW switching valve "Open"
Connection J3 (potential-free relay: normally open B-B1) - AUX
Connection J3 (potential-free relay: Changer A-A1/A-A2) - AUX
Output J10 (A1P power supply)
Output J17 (pin 3) - relay K2 (RTX-EHS) output XBUH1 T2
Output J17 (pin 2) - relay K1 (RTX-EHS) output XBUH1 T3
Output J17 (pin 4) - relay K3 (RTX-EHS) output XBUH1 T1
Activation of automatic ventilation of the Daikin Altherma EHS(X/H) and the
connected HC.
Deactivated
Start of the ventilation function
Factory
Incre-
Access
setting
ment
BE HF
Off
1 min
E
E
Off
-
E
E
03:30
15 min
N
E
65 °C
1 °C
N
E
Factory
Incre-
Access
setting
ment
BE HF
-
-
N
E
-
N
E
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN