3.3 Exploded view appliance

1 Service connector
2 Display and 4 control buttons
3 Control board
4
5 Preheater
6 Heat exchanger
7
8 Outdoor temperature sensor
9 Indoor temperature sensor
10 Bypass valve
11 Condensate discharge
12 Extract fan
13 Supply fan
14 Modular connector multiple switch X2
15 Connector eBus X1
16 Connector X15
17 Connector X14
18 Mains cable 230 V
19 Connection to postheater
Computer connection for service purposes.
Interface between user and control electronics.
Contains the control electronics for the basic functions.
Heats up the outdoor air when there is a risk of freezing for the heat exchanger
Ensures heat transfer between input and output air
Filters outdoor are supplied to the dwelling
Measures outside air temperature.
Measures the dwelling air temperature
Sends the air through or around the heat exchanger (For the 3/1 and 4/0 this
valve is in the upper part of the appliance)
Connection condensate discharge (Kit comes separately with the appliance)
Discharges air from the dwelling to the atmosphere.
Feeds fresh air into the dwelling.
Connection for eBus control
Contains the various control inputs and outputs; only for Plus version
Connection postheater; only for Plus version (accessible after taking off the
display cover)
Gland power cable 230 volt
Gland 230 V cable to postheater; only for Plus version